Steel space frame is generally designed as spatial grid structures, checked for Ultimate Limit State (strength & stability) and Serviceability Limit State (deflection); including fundamental combinations and characteristic combinations.

1. Load Notation

• Dead load: G_k (self-weight, roofing, ceiling, etc.)

• Live load: Q_k (roof live load; 0.5kN/㎡ for non-accessible roof, 2.0kN/㎡ for accessible roof)

• Snow load: S_k (roof live load and snow load shall not be applied simultaneously; take the larger one)

• Wind load: W_k (wind suction usually governs for steel space frames)

• Temperature effect: T_k (temperature difference, mandatory for long-span frames)

• Earthquake action: E_k (usually not required for small & medium roof frames; required for long-span or important buildings)
2. Ultimate Limit State — Fundamental Combinations (for strength and stability check)

Partial factors:
\gamma_G=1.2 (when dead load is favourable, \gamma_G=1.0, applies to wind suction case)
\gamma_Q=1.4 (for live load, snow load, بار باد, temperature effect)

Common governing combinations (directly usable in 3D3S):

1. 1.2G + 1.4Q (live load controlled)

2. 1.2G + 1.4S (when snow load > live load)

3. 1.2G + 1.4W (wind pressure)

4. \boldsymbol{1.0G + 1.4W} (wind suction — the most critical load case for steel space frame. Dead load is favourable, so γG=1.0. Tension members may turn into compression members and cause stability failure.)

5. 1.2G + 1.4Q + 1.4×0.6W (live load + باد)

6. 1.2G + 1.4S + 1.4×0.6W (snow load + باد)

7. 1.2G + 1.4Q + 1.4T (dead + live + temperature)

8. 1.2G + 1.4W + 1.4×0.6T (باد + temperature)

With earthquake action (long-span / important structures)

1.2G + 1.3E + 0.7×1.4Q, etc. For ordinary coal sheds and common roof steel space frames, seismic combinations are often not mandatory, subject to local drawing review requirements and seismic classification.

3. Serviceability Limit State — Characteristic Combinations (deflection check only, no strength check)

All partial factors = 1.0. Deflection limit for steel space frame: L/250
1. G_k + Q_k
2. G_k + S_k
3. G_k + W_k
4. G_k + Q_k + 0.6W_k
4. Common Pitfalls for Site & طراحی

1. If wind suction exceeds dead load, the top chord may be uplifted; tension members change to compression members, stability governs. This is the primary risk of steel space frame.

2. Do not superimpose live load and snow load in software; select the larger one.

3. Temperature effect: generally required for exposed long-span steel space frame of open workshops; may be waived for small indoor spans, subject to span and drawing review.

4. Wind shape factor varies greatly for roof frames, overhangs, staggered roofs and coal sheds; coal sheds have large negative pressure.

5. Deflection shall only be checked under characteristic combinations. Do not use fundamental combinations for deflection evaluation, otherwise results will be underestimated and misleading.

5. Tips for 3D3S Setting

Load combination type: spatial grid structure. Check the built-in combinations carefully. Pay special attention to whether the case 1.0G+1.4W is automatically generated. Many engineers miss this load case, which leads to checking failure later.